Air handling unit (AHU) Qualilfication and clean room Classification :
Ensure the AHU is in switch ON.
Switch ON the anemometer and
allow it to some time for stabilization.
Ensure that anemometer
measuring unit is in FPM mode.
To change the measuring unit
mode, press the UNIT button till display shows FPM.
Take the readings at five
locations at each filter as per below mentioned diagram.
|
- Position the probe pointing towards airflow. Locate the probe approximately 1/6 diagonal distance and measure velocities from each corner.For clean room measurement shall be taken at a distance of 150 mm from the filter face. Take the readings after stabilization or take the average reading of oscillating value shown in the display.
Procedure to Calculate the Air changes
Calculate the supply grill area
A= Length (in ft) x Width (in ft).
Calculate the supply grill
Average velocity V= (V1+V2+V3+V4+V5 ) /5.( in
ft/min) .
Calculate the air flow
delivered by each supply grill in CFM =
A x V (in CFM).
Find the total quantity of
supply air delivered in to the room in CFM by adding all supply grills air flow CFM.
Calculate the air changes by
below given formula.
Air changes per hour = Total supply air flow rate (CFM) in the clean room x 60
Volume of the clean room (cu. ft)
Example :
Air velocity = 100 feet
per min
Air Flow = Velocity Ft/
min x grill area(Ft2)
=
100 x 4 =400 Cubic feet per min(CFM)
If room has two supply grills,
sum the two air flows = 400+ 400= 800 CFM
Air changes = Air flow x 60
Room volume(Ft3 )
=800 Ft3x 60 min
1000 Ft3
= 48 Air changes per hour (Limit : Not less than 25 air
changes per hour for ISO 8)
There are 5 tests during AHU
Qualification.
S.NO
|
Test
|
Frequency
|
Instruments used
|
Acceptance criteria
|
1
|
Air Changes
|
For every six months
(on or before 7 days)
|
Anemometer
for Velocity of air
|
Not
less than 25 air changes per hour
|
2
|
Particle count “At Rest Condition”
|
Particle counter
|
Not more than 3520000 for ISO 8
There is an equation to estimate particle limit.
|
|
3
|
HEPA Filter Integrity Test
(Leak Test)
|
Aerosol Photometer and Aerosol generator
using compressed air
|
No leak should be observed
Not more than 0.01% leak
|
|
4
|
Recovery test
|
For every one year
(on or before 15 days)
|
Particle
counter
|
Recovered
within 15 minutes, after polluting the room with aerosols
|
5
|
Air flow pattern
|
Dry ice in hot water to generate SMOKE
|
Uni-directional and positive and negative
pressure should be indicative.
|
Regards,
Bujji Reddy.
9676749937